Remote Controlled
The analog outputs on the XTDL-HT™ can be remotely controlled via its Modbus interfaces. In addition
to configuring the channels remotely, the instrument allows the Modbus master to directly control its
analog outputs. This allows the DCS system to control another device via the XTDL-HT™ without setting
up a Remote Terminal Unit.
Remotely change the analog output signal
Set Modbus register Analog Output Variable to 32768
Set Modbus register Analog Output Value to the
desired digital-to-analog converter input value
Channel 1
Channel 2
Analog Output Variable
Register 40405
Register 40415
Analog Output Value
Register 40410
Register 40420