Cosa-xentaur Xentaur XDTL-HT Manuel d'utilisateur Page 46

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 45
46
Register
Number
Address
Access
Level
Data
Type
Description
Values
40305
304 (130h)
Admin
16-bit
Relay 1 mode
bit 0: Polarity (0=normally closed, 1=normally
opened)
bits 1-8: Variable ID
4
bit 9: Assert when variable below low threshold
(0=disabled, 1=enabled)
bit 10: Assert when variable above high
threshold (0=disabled, 1=enabled)
bit 11: Self cleared (0=disabled, 1=enabled)
bit 12: Unused
bit 13: Assert on fault (0=disabled, 1=enabled)
bit 14: Time controlled (0=disabled, 1=enabled)
bit 15: Remote controlled (0=disabled,
1=enabled)
40306
305 (131h)
Admin
16-bit
Relay 2 mode
See Relay 1 mode
40307
306 (132h)
Admin
16-bit
Relay 3 mode
See Relay 1 mode
40308
307 (133h)
Admin
16-bit
Relay 4 mode
See Relay 1 mode
4
Valid relay variable ID’s are:
Value
Description
Value
Description
Value
Description
Value
Description
0
Off
5
Analog output 1 valid
67
Enclosure temperature
120
PID 1
1
System fault
6
Analog output 2 valid
68
User input 1
121
PID 2
2
Calibration fault
64
Dewpoint
69
User input 2
122
PID 3
3
Calibrating
65
Sample temperature
70
User input 3
123
PID 4
4
Validating
66
Sample pressure
71
User input 4
Vue de la page 45